            All items required
Underground
	- Inspection of piping
 
	- Inspection of thrust blocks
 
	- Witness hydrostatic pressure test
 
	- Witness flush
 
Overhead
	- Inspect piping
 
	- Inspect hangers
 
	- Inspect sway bracing
 
	- Witness hydrostatic pressure test
 
Acceptance
	- Test flow switches
 
	- Test tamper switches
 
	- Test interconnection to alarm system
 
	- Witness flow test at rooftop (standpipe)
 
	- Witness fire pump test
 
	- Witness pop-off test (kitchen hood systems)
 
	- Witness concentration test (clean agent)
 
Fire Alarm Systems
	- Rough inspection
 
	- Pre-test in the presence of the electrical inspector
 
	- Duct detector pressure differential test
 
	- Indicating device audibility test
 
	- 100% final acceptance test
 
Fire Assemblies
	- Inspect labels on all fire assemblies (doors, windows, dampers, etc.)
 
	- Inspect installation of fire assemblies
 
	- Test automatic closing device
 
	- Mechanical inspector drop-tests 100% of dampers
 
	- Fire inspector drop-tests 100% of 2-hour and 10% of 1-hour dampers
 
	- Fire doors must self-close and latch after gaskets have been installed
 
Emergency Generators
	- Inspect load bank test results
 
	- Witness power outage simulation test
 
	- Inspect all components, equipment, fixtures, etc.
 
Elevators
	- Inspect hoistway
 
	- Inspect and test hoistway vent
 
	- Witness firefighter recall, Phases I and II
 
	- Test emergency communications system
 
Occupancy and Final Inspection
	- Fire Extinguishers in place
 
	- Emergency Plan posted
 
	- Exits clear and unobstructed
 
	- Issuance of Certificate of Occupancy